Intelligent Demand-Controlled Ventilation with Flair
Demand-controlled ventilation (DCV) adjusts outdoor airflow to changing occupancy while maintaining the ventilation a space requires.
A CO₂-only control strategy responds to an occupancy-related signal. It cannot see smoke particles or chemical emissions.
ThinkLite Flair raises the standard for ventilation decisions. CO₂, particle counts and TVOCs combine with outdoor-air information to support a coordinated BMS strategy. Room demand and incoming air quality shape the same response.
Same room. Two approaches.
See how fixed airflow and demand-led ventilation respond to changing room conditions and outdoor air quality.
Fixed ventilation
- A preset damper opening keeps outdoor air flowing at the same setting.
- As occupancy falls, the system can continue conditioning more air than the room needs.
- During a pollution event, incoming air can also carry particles indoors.
Demand-led ventilation
- Flair supplies room readings and calculated demand.
- The building management system (BMS) combines those inputs with outdoor conditions to execute a configured response.
- When outdoor air is suitable, the damper adjusts to ventilation demand.
- During smoke events, the sequence can limit excess intake and coordinate filtration while maintaining required ventilation and building pressure.
Flair readings → BMS control sequence → Damper and compatible air-cleaning equipment
Add ICON to both rooms
- ICON filters recirculated room air.
- Automatic operation through the BMS requires a compatible, commissioned control connection.
- Ventilation continues to manage CO₂.
The energy bars illustrate outdoor-air conditioning demand. Total system energy also includes fans and ICON operation.
Outdoor conditions input Clean air
Fixed ventilation
Preset outdoor airflowA fixed setting continues bringing in outdoor air at the preset rate, even as room demand changes.
The preset airflow continues.
Outdoor-air damper Fixed opening
- Air-quality view
- Changing conditions
- CO₂
- Responds to ventilation
- Particles
- Depend on incoming air
One airflow setting as conditions change.
Demand-led
Responds to the roomDemand-led ventilation adjusts outdoor airflow while maintaining the required minimum. ICON adds particle filtration; ventilation continues to manage CO₂.
Monitor indoor conditions
Outdoor-air damper Adjusts with demand
- Air-quality view
- Changing conditions
- CO₂
- Responds to ventilation
- Particles
- Filtration available
Ventilation for CO₂. Optional filtration for particles.
ASHRAE Standard 241-2023 sets equivalent clean airflow requirements for infection risk management, using ventilation, filtration and qualifying air cleaning. Compliance with the applicable ventilation standard is a prerequisite. Energy bars compare relative outdoor-air conditioning demand, not measured total electricity use; ICON also consumes power. ASHRAE guidance
Match ventilation to the way a room is used
A meeting room fills for a morning discussion, then sits nearly empty. A fixed outdoor-air setting can keep the system working at the same rate throughout the day.
DCV adjusts the occupant-related ventilation component as demand changes. Under ASHRAE’s Ventilation Rate Procedure, the required area-based component remains. That balance reduces excess intake while maintaining the outdoor air the occupied space needs. ASHRAE 2025 Handbook—Fundamentals, Chapter 16
Reducing excess airflow is only part of the job. Flair equips your controls team to address another question—what happens to the room when that outdoor air enters?
The dangerous blind spot in CO₂-only DCV
Rising indoor CO₂ can trigger a request for more outdoor air. If wildfire smoke, traffic exhaust or diesel generator soot is near the intake, that response can bring hazardous particles indoors.
Without an outdoor-pollution input and suitable filtration, the system can lower CO₂ while making the particle problem worse. A low CO₂ reading cannot establish clean indoor air. ASHRAE Position Document on Indoor Carbon Dioxide, 2025
Your BMS cannot respond to pollution it has no information about.
Flair brings CO₂ + particle counts + TVOCs into a coordinated control strategy. Each signal addresses a different part of the ventilation decision.
CO₂ establishes ventilation context.
- Trends help assess occupant-related ventilation demand.
- Interpretation depends on outdoor CO₂, activity, airflow and room conditions.
Particle counts expose pollution that mass alone can understate.
- Flair counts particles down to approximately 0.1 µm.
- Small particles contribute little mass individually, so their number can rise without a large change in PM₂.₅.
- Particle count measures number per volume, such as counts/ft³.
- PM measures mass in µg/m³.
TVOCs reveal changing chemical emissions.
- Total volatile organic compounds provide an aggregate signal that can flag emissions from cleaning, furnishings and other sources.
- The reading supports investigation of the mixture.
- Identifying individual chemicals requires compound-specific measurements. EPA technical overview of VOCs
Together, the three signals inform a response a standalone CO₂ sensor cannot provide.
- Flair supplies the measurements and CO₂-led calculated demand.
- The configured BMS sequence determines when to adjust outdoor air, prioritize filtration or flag a chemical event for investigation.
Outdoor conditions complete that decision. Nearby station data provides context. Intake-level monitoring helps investigate pollution specific to the building. Your controls team defines how these inputs work together, including the response when signals conflict.
The ThinkLite Health Index adds health-oriented context to measured conditions, helping teams prioritize attention. Available readings and indices depend on the selected Flair configuration. Explore Flair monitoring
How demand-controlled ventilation saves energy
Every unnecessary unit of outdoor air can add heating, cooling or dehumidification work when it needs conditioning. DCV reduces that excess by matching intake to demand within the building’s ventilation requirements.
The control sequence should coordinate outdoor-air demand, economizer operation, humidity and filtration. Suitable outdoor air can provide free cooling. During pollution events, the system should manage intake and filtered recirculation together. Supply-fan savings depend on whether the sequence also reduces total airflow. ASHRAE 2025 Handbook—Fundamentals, Chapter 16
ICON adds ULPA particle capture within the room. Its carbon pre-filter provides a stage for adsorption of suitable gaseous contaminants, with performance dependent on the compound and filter condition. ICON does not remove CO₂ or replace required outdoor-air ventilation. Explore ICON
Build the sequence around applicable ventilation requirements and the building’s smoke-response plan. Commission airflow, damper response and filtration together so energy control supports the people using the space. ASHRAE Standard 62.1-2025 overview, ASHRAE wildfire guidance
Connected to your building. Visible to your team.
Flair shares room data with local building controls. The BMS applies the configured rules and commands the connected equipment.
Optional cloud API and MQTT access extend that information to your applications. Airlytics® brings readings and historical trends together so teams can compare rooms, investigate recurring conditions and review the response to an adjustment.
FlairRoom-level DCV valueMeasure conditions → Apply the BMS sequence → Review the response
Work with the systems you already use
Choose the connection that fits your building and selected Flair configuration.
- Local BACnet
- — BACnet/IP and BACnet MS/TP.
- Local Modbus
- — Modbus TCP/IP and Modbus RTU over RS-485.
- Application access
- — Local MQTT and optional cloud API or MQTT.
Local BACnet and Modbus operation can work without the cloud. Your controls team maps Flair’s calculated demand and supported readings to the equipment response, including required airflow, pollution priorities and handling of missing or stale data.
Confirm sensor placement, calibration and equipment compatibility during commissioning. Then test the response under changing demand and outdoor conditions.
Explore Flair IAQYour DCV questions, answered
Can a basic CO₂ sensor deliver Flair’s approach to DCV?
No. It measures CO₂. It cannot measure chemical off-gassing, smoke particles or submicron particulate. Opening dampers on CO₂ alone can degrade indoor air quality when polluted outdoor air enters.
A basic sensor can support occupancy-based DCV. Flair adds particle and chemical information so the configured BMS strategy can address a wider set of conditions.
Why does particle count matter in a DCV strategy?
Small particles can be numerous while contributing little mass. Counts make that burden visible. Compare indoor trends with outdoor or intake conditions to guide damper and filtration decisions. An economizer also needs an outdoor-air-quality strategy when pollution affects otherwise suitable cooling air.
Can Flair connect to a local BMS without the cloud?
Yes. Supported BACnet and Modbus connections allow local data exchange. Enable the interfaces required for your installation. Cloud access is optional.
Is a DCV value the same as required airflow?
No. It expresses calculated demand. The BMS maps that value to airflow and equipment commands under the building’s configured requirements.
Can ICON replace outdoor-air ventilation?
No. ICON captures particles from recirculated air. Required ventilation continues, including the outdoor air needed to manage CO₂. ASHRAE Standard 241 combines qualifying air cleaning, filtration and ventilation for infectious-aerosol control, with applicable ventilation requirements as a prerequisite. ASHRAE Standard 241 fact sheet
Where does the energy-saving opportunity come from?
Start with occupied periods when outdoor airflow exceeds demand. Adjusting that intake reduces avoidable conditioning load. Coordinate fan controls and economizer operation to capture the opportunities available in your system.
What affects the cost of a DCV integration?
Your existing controls, available connections, sensor configuration and commissioning needs determine the scope. A review of those elements establishes the practical next step.
Research behind the article
- ASHRAE: 2025 Handbook—FundamentalsChapter 16 · Ventilation and Infiltration · Dynamic Control of Ventilation.
- ASHRAE: Standard 62.1-2025Official 2025 edition overview · Confirm applicable requirements with your design professional.
- ASHRAE: Indoor Carbon Dioxide position documentRevised February 12, 2025 · CO₂, ventilation and indoor air quality.
- ASHRAE: Standard 241 and equivalent clean airflowVentilation, filtration and air cleaning in an infectious-aerosol control strategy.
PLAN YOUR NEXT STEP
Make your air data work for your building
Bring your room requirements, existing controls and energy goals. ThinkLite Air can help you select the Flair measurements, Airlytics® views and purification options that fit your project.
For ongoing support, explore CLAAS—Clean Air as a Service. The service combines hardware, software and air-quality expertise around an agreed project scope.